Duty cycling of centrifugal chillers has been considered an effective method for demand side management.
Full scale experiments were performed to identify that unloading was a necessary step so that excessive mechanical wear would not occur due to cycling operation.
On the other hand, reciprocating and screw compressors can adapt to cycling operation successfully.