The Effects of Internal and External Irreversibility of a Vapor Compression Refrigeration Cycle @@ @@
The Effects of Internal and External Irreversibility of a Vapor Compression Refrigeration Cycle @@ @@
FuEjen Wang, JengEshing Chiou @

The concept of finiteEtime thermodynamics is employed to investigate the optimal refrigeration rate for an irreversible refrigeration cycle. The heat transfer between the system (internal) fluid and cooling (external) fluid takes place at the actual heat exchanger, which has the finiteEsize heat transfer area and the realistic heat transfer effectiveness. The internal irreversibility results from the compression process and the expansion process are also considered. The optimal refrigeraion rate is calculated and expressed in terms of the irreversibility parameter (Ir), coefficient of performance (COP), the time ratio (ƒÁ) of heat transfer processes and the effectiveness of heat exchanger. The derived COP which consider both the external and internal irreversibility can thus be employed as the benchmark value for a practical refrigeration cycle, and the parametric study can provide the basis for both determination of optimal operating conditions and design of a practical refrigeraion cycle.